To test this hypothesis a generic CFD analysis was performed using a compressible two phase flow solver in OpenFOAM. A maximum pressure drop over the vent pipe of 0.8 bar was found. Assuming the pressure loss is entirely converted to heat, the gas temperature is increased by about 80 °C. This temperature increase exceeds the maximum design temperature in most cases, which could possibly lead to deformations for certain pipe materials.
#Deluge #sprinkler #ventpipe #compressible #two-phase-flow #pressurewave #CFD #OpenFOAM #Dynaflow #Helyx #Temperaturerise #friction #deformation